SERVICING: CALGARY & THE CMR
REZNOR FURNACE REPAIR
Seeking high-quality, reliable Reznor furnace and unit heater repair or installation in Calgary? One Stop HVAC is your go-to for prompt, same-day services for all Reznor products, ensuring your comfort and satisfaction. Call us today to schedule your appointment!
Same / Next Day
Service 24/7
Rating 5/5
Google Reviews
Licensed TSSA
Technicians
Served Over 1000
Local Residents
Get Your Free
Estimate Today
Great Prices
Guaranteed
REZNOR HVAC SERVICES
Please Select One Of The Following:
24/7 Emergency Reznor Furnace Repair and Installation
The last thing you need in the winter months is a failing heating system. Ensure your home or office stays warm with One Stop HVAC’s expert Reznor furnace repair and installation services in Calgary. Our team of experienced technicians excels in diagnosing and fixing any issue, as well as providing top-notch Reznor furnace installation. We also offer same-day installation for Reznor furnaces.
We’re dedicated to offering reliable, efficient solutions for your heating needs. You can count on us for seamless service that keeps your space warm and welcoming, year-round!
Reznor Furnaces are manufactured by Nortek Global HVAC.
Reznor Furnaces were originally produced in Mercer, Pennsylvania, but since then, their production has spread throughout North-America and Europe.
To maintain optimal function over a long period of time, your HVAC systems should be inspected, cleaned, and serviced once a year. This will ensure that your furnace is kept in an optimal condition to last as long as possible.
Reznor does provide replacement parts for some of its older model furnaces, including some that have been in continuous working condition since the 1940s.
Click here to check if your furnace has replacement parts available.
Experienced Reznor Unit Heater Installation and Repair
Keep your space perfectly heated with One Stop HVAC’s professional repair and installation services for Reznor unit heaters. Our technicians can provide same-day repairs for Reznor unit heaters, Reznor garage heater installation, and ongoing Reznor unit heater support.
Whether you’re looking to upgrade your heating system with a new Reznor unit or need swift repairs to keep your current unit heater running efficiently, we provide tailored solutions that meet your specific requirements. Trust us to ensure your unit or garage heater delivers optimal performance and energy efficiency.
There are many factors to consider when evaluating how large a garage heater you’ll need, including insulation, ceiling height, and the temperature you’d like to maintain for the space in question.
A good rule of thumb is 30-50 BTUs per square foot of space you’re trying to heat.
Reznor unit heaters have one of the longest warranty periods in the industry.
On parts, the warranty lasts 5 years. On the heat exchanger, the warranty extends for 10 years.
In general, it is not advisable to leave a unit heater on overnight. Doing so can create a significant fire hazard if the unit should overheat, tip over, or short-circuit.
That depends largely on fuel capacity, remaining fuel, and how hard the heater has to work to maintain the desired temperature.
Generally speaking, a unit heater will operate without issues for a period of 15-20 years, unless it experiences a specific failure.
Reznor Furnace LED Light Error Codes
Meaning:
Thermostat demand signal Y is present, but compressor is not running.
Troubleshooting Information:
• Compressor protector is open
• Check for high head pressure
• Check compressor supply voltage
• Outdoor unit power disconnect is open
• Compressor circuit breaker or fuse(s) is open
• Broken wire or connector is not making contact
• Low pressure switch open if present in system
• Compressor contactor has failed open
Meaning:
Long Run Time Compressor is running extremely long run cycles.
Troubleshooting information:
• Low refrigerant charge
• Evaporator blower is not running
— Check blower relay coil and contacts
— Check blower motor capacitor
— Check blower motor for failure or blockage
— Check evaporator blower wiring and connectors
— Check indoor blower control board
— Check thermostat wiring for open circuit
• Evaporator coil is frozen
— Check for low suction pressure
— Check for excessively low thermostat setting
— Check evaporator airflow (coil blockages or return air filter)
— Check ductwork or registers for blockage
• Faulty metering device
— Check TXV bulb installation (size, location and contact)
— Check if TXV/fixed orifice is stuck closed or defective
• Condenser coil is dirty
• Liquid line restriction (filter drier blocked if present in system)
• Thermostat is malfunctioning
— Solenoid plug not connected
— Y2 not wired at Comfort Alert
— Check thermostat sub-base or wiring for short circuit
— Check thermostat installation (location, level)
• Comfort Alert failure
Meaning:
System Pressure Trip
• High head pressure
— Check high pressure switch if present in system
— Check if system is overcharged with refrigerant
— Check for non-condensable in system
OR
Discharge or suction
• Condenser coil poor air circulation (dirty, blocked, damaged)
OR
Pressure out of limits
• Condenser fan is not running
— Check fan capacitor
— Check fan wiring and connectors
— Check fan motor for failure or blockage
OR
Compressor overloaded
• Return air duct has substantial leakage
• If low pressure switch present in system, check Flash Code 1
information
Meaning:
Short Cycling / Compressor is running only briefly
Troubleshooting Information:
• Thermostat demand signal is intermittent
• Low line voltage (contact utility if voltage at disconnect is low)
• Excessive liquid refrigerant in compressor
• Compressor bearings are seized
Meaning:
Locked Rotor
Troubleshooting Steps:
• Run capacitor has failed
• Low line voltage (contact utility if voltage at disconnect is low)
• Check wiring connections
• Excessive liquid refrigerant in compressor
• Compressor bearings are seized
• Measure compressor oil level
Meaning:
Open Circuit
Troubleshooting Information:
• Outdoor unit power disconnect is open
• Compressor circuit breaker or fuse(s) is open
• Compressor contactor has failed open
— Check compressor contactor wiring and connectors
— Check for compressor contactor failure (burned, pitted or open)
— Check wiring and connectors between supply and compressor
— Check for low pilot voltage at compressor contactor coil
— High pressure switch is open and requires manual reset
• Open circuit in compressor supply wiring or connections
• Unusually long compressor protector reset time due to extreme
ambient temperature
• Compressor windings are damaged
— Check compressor motor winding resistance
Meaning:
Open Start Circuit
Current only in run circuit
Troubleshooting Steps:
• Run capacitor has failed
• Open circuit in compressor start wiring or connections
— Check wiring and connectors between supply and the
compressor S terminal
• Compressor start winding is damaged
— Check compressor motor winding resistance
Meaning:
Open run circuit
Current only in start circuit
Troubleshooting Information:
• Open circuit in compressor run wiring or connections
— Check wiring and connectors between supply and the
compressor R terminal
• Compressor run winding is damaged
— Check compressor motor winding resistance
Meaning:
Welded Contactor
Compressor always runs
Troubleshooting Steps
• Compressor contactor has failed closed
• Thermostat demand signal not connected to module
Meaning:
Low Voltage
Control circuit < 17VAC
Troubleshooting Steps:
• Control circuit transformer is overloaded
• Low line voltage (contact utility if voltage at disconnect is low)
• Check wiring connections
Please note that these LED error codes are general and may not cover every possible variation. Always refer to your Reznor furnace manual or consult a professional technician for accurate diagnosis and resolution.
Reznor Unit Heater Circuit LED Error Codes
Normal Operation, No call for heat.
Normal Operation, Call for heat
System Lockout, Failed to detect or sustain flame
Pressure Switch Open or Closed
High Limit or Flame Rollout Switch Open
Flame Sensed and Gas Valve not energized
Internal Failure – Replace the circuit board